CAMPUS360Smart City Solution by Senzary

Overflow Risk

Sites ranked by how soon they spill — not alphabetically, not by sensor ID.

Prevent sanitary sewer overflows.

A level reading is not the objective. Stopping the spill is. Every view here is ordered by how close a site is to surcharging, what is driving it, and which crew is already moving — because an SSO is measured in gallons to surface water and consent-decree exposure, not in feet of water.

Imminent
1

Surcharge within 2 hr

High Risk
2

Surcharge within 8 hr

Gallons Exposed
1.0M

If unattended

Mean Warning
6.4 hr

Lead time before surcharge

Ranked by Time to Surcharge
SiteRiskTime to SurchargeHeadroomCapacity UsedRise RateGallons at RiskCorrelated Cause
SW 8th St & 137th Ave
SC-0203 · West Kendall
Imminent
0.2 hr0.1 ft
98%
+0.42 ft/hr480KLift station running septic — drawdown stalled
Biscayne Blvd & NE 54th
SC-0187 · Little River
High
3 hr1.2 ft
80%
+0.40 ft/hr310KFOG slug from upstream Restaurant Row discharge
Coral Way & SW 22nd Ave
SC-0311 · Miami River
High
7.2 hr1.3 ft
76%
+0.18 ft/hr225KInflow following 1.2 in rainfall event
FOG Interceptor — Restaurant Row
IQ-1014 · Miami River
Moderate
9 hr2.8 ft
30%
+0.31 ft/hr90KGrease discharge event — fluorescence spike
Pump Station 214 — Wet Well
IQ-1002 · Little River
Moderate
18.6 hr4.1 ft
49%
+0.22 ft/hr640KImpeller wear — drawdown cycle 38% longer than baseline
US-1 & SW 152nd St
SC-0298 · South Dade
Watch
90 hr3.6 ft
49%
+0.04 ft/hr180KWithin normal diurnal band
NW 27th Ave & 79th St
SC-0142 · Little River
Watch
195 hr3.9 ft
35%
+0.02 ft/hr140KBaseline stable, 3 yr history
SW 88th St & 117th Ave
SC-0359 · West Kendall
No Data
unknownn/a200KNo transmission — battery or antenna
NE 163rd St & Biscayne
SC-0334 · North Dade
Stable
not rising3.7 ft
43%
0.00 ft/hr150KBaseline stable
Pump Station 118 — Wet Well
IQ-1007 · West Kendall
Stable
not rising5.8 ft
28%
-0.05 ft/hr520KMotor current and vibration nominal
NW 7th Ave & 119th St
SC-0261 · Miami River
Stable
not rising3.9 ft
29%
-0.01 ft/hr120KFree-flowing
Plant Headworks — Gas Array
IQ-1021 · Central District
Stable
not risingn/an/aWorker-safety exceedance — confined space entry hold
Why this ordering is the product
Level is not the answer

A site at 5.9 ft is not automatically worse than one at 4.8 ft. What matters is headroom against its own surcharge depth and how fast it is closing.

Rate beats threshold

A threshold alarm fires when it is already too late. Rate of rise converts a reading into hours of lead time a crew can actually use.

Cause beats alert

Every row names what is driving the rise — FOG slug, stalled drawdown, rainfall inflow — because the crew needs a task, not a number.